CMUO 6-10KVA
Features:
- Advanced DSP and 3-level technology
- Output power factor 1.0
- Active power factor correction (APFC), input power factor up to 0.99
- High efficiency 95% (up to 98% in ECO mode)
- Advanced digital parallel technology
- Wide input voltage range (110 ~ 288 Vac) and frequency range (40 ~ 70 Hz)
- 50 / 60 Hz frequency auto sensing
- Two modes of frequency conversion: 50 Hz input / 60 Hz output or 60 Hz input / 50 Hz output
- Dual-input design, supporting independent bypass
- Flexible battery configuration (settable 16 - 20 pcs batteries)
- Digitally controlled charger
- High charging current available (Max. 12 A)
- Charging voltage and current configured by demands
- Linear derating in low voltage input reducing battery discharging times, extending the service life of battery
- Intelligent battery management, automatic floating / equalizing charge control, charger dormancy control, increasing battery life by 50%
- Ability to switch on the UPS with batteries
- Settable delayed start time when mains power is restored, reducing the impact on power grid or generator
- Fan speed varies intelligently with temperature, reducing noise and extending its service life
- Equipped with self-aging function
- Compact internal layout, miniaturized the complete unit for small footprint
- LCD+LED display, multi-functional keys operation, friendly human-machine interface
- Powerful background software for parameters configuration
- Advanced multi-platform communications: RS232, USB, RS485, SNMP and dry contacts communication interfaces
- Effective software and hardware protection function, robust self-diagnostic function, and abundant event log for check
- Available Options
- RS232 and smart card slot included
- Optional parallel function, battery temperature compensation, SNMP card, USB, RS485 card, dry contacts, EMD, and SMS alarms
Where to buy Compare

MODEL | CMUO-6KVA | CMUO-10KVA | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Capacity | 6 kVA / 6000 W | 10 kVA / 10000 W | |||||||||
INPUT | |||||||||||
Input wiring | Single-phase three-wire (1Φ + N + PE) | ||||||||||
Rated voltage | 208 / 220 / 230 / 240 Vac | ||||||||||
Voltage range | "110 ~ 176 Vac (linear derating between 50% and 100% load); 176 ~ 288 Vac (no derating)" | ||||||||||
Rated frequency | 50 / 60 Hz (auto-sensing) | ||||||||||
Frequency range | 40 ~ 70 Hz | ||||||||||
Power Factor | ≥ 0.99 | ||||||||||
Bypass Voltage Range | (- 40%, +15%) (settable) | ||||||||||
Total harmonic distortion (THDi) | ≤ 5% | ||||||||||
OUTPUT | |||||||||||
Output wiring | Single-phase three-wire (1Φ + N + PE) | ||||||||||
Rated voltage | 208 (PF=0.9) / 220 / 230 / 240 Vac | ||||||||||
Voltage regulation | ± 1% | ||||||||||
Frequency | Synchronized to bypass in mains mode; 50 / 60 Hz ± 0.1% Hz in battery mode | ||||||||||
Waveform | Sinusoidal | ||||||||||
Crest Factor | 3:1 | ||||||||||
Total Harmonic Distortion(THDi) | "≤ 1% (linear load); ≤ 4% (non-linear load) " | ||||||||||
Transfer Time | AC mode and battery mode:0ms | ||||||||||
Inverter model and bypass mode:0ms(Typical) | |||||||||||
Overload Capability | 105% ~ 110% for 10 min, 110% ~ 125% for 1 min,126% ~ 150% for 30 s | ||||||||||
125%-150%:Transfer to bypass after 30 s; | |||||||||||
Efficiency | |||||||||||
AC Mode | 92% | ||||||||||
Battery Mode | 91% | ||||||||||
ECO Mode | 98% | ||||||||||
BATTERY | |||||||||||
DC Voltage | 192 Vdc (192 ~ 240 Vdc settable) | ||||||||||
Number of battery | 16 pcs (16 ~ 20 settable) | ||||||||||
Number of battery | 12 V / 7 Ah × 16 | 12 V / 9 Ah × 16 | |||||||||
Charging current | "Standard model: 1 A; Long time model: 5 A (default),1 ~ 5 A settable; 12 A (optional; PF 0.9) " | ||||||||||
Recharge time | "Standard model: 90% capacity restored in 8 hours; Long time model: depend on the capacity of battery | ||||||||||
SYSTEM | |||||||||||
Efficiency | ≥ 94% at 100% load, max. 95% at 60% load, ≥ 98% in ECO mode | ||||||||||
Transfer time | 0 ms | ||||||||||
Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure | ||||||||||
Max. number of parallel connections | 4 | Protections | Short-circuit, overload, overtemperature, battery low voltage, overvoltage, undervoltage and fan failure | ||||||||
Communications | RS232 (standard), USB / RS485 / dry contacts / SNMP / battery temperature compensation (optional) | Display | LCD + LED | ||||||||
Display | LCD + LED | ||||||||||
OTHERS | |||||||||||
Operating temperature | 0℃ ~ 40℃ ) | ||||||||||
Storage temperature | (-25, 55)°C (without batteries) | ||||||||||
Relative humidity | 0 ~ 95% (non-condensing) | ||||||||||
Altitude | ≤ 1000 m, derating 1% for each additional 100 m | ||||||||||
IP rating | IP 20 | ||||||||||
Noise level at 1m | ≤ 55 dB | ≤ 58 dB | |||||||||
PHYSICAL | |||||||||||
Dimension(mm)W*D*H | 191 × 465 × 711 (S), 191 × 465 × 350 (H) | 191 × 495 × 711 (S), 191 × 495 × 350 (H) | |||||||||
Packing Dimmension(mm)W*D*H | 310 × 654 × 941 (S), 318 × 595 × 475 (H) | 310 × 685 × 941 (S), 318 × 617 × 475 (H) | |||||||||
Net Weight(kg) | 53 (S), 14.5 (H) | 62 (S), 16.5 (H) | |||||||||
Gross Weight (kg) | 61 (S), 16 (H) | 70 (S), 18 (H) |