CMBT-12V-18 Ah
Cells Per Unit | 6 | |
Voltage Per Unit | 12 | |
Nominal Capacity | 18 Ah@20hour-rate to 1.75V per cell @25C | |
Weight | Approx. 5.0 Kg (Tolerance±4.0%) | |
Internal Resistance | Approx. 14 mO | |
Terminal | F3(M5)/F13(M5) | |
Max. Discharge Current | 180A (5 sec) | |
Short Circuit Current | 720A | |
Design Life | 6~8 years (Float charging) | |
Recommended Maximum Charging Current | 5.4 A | |
Reference Capacity |
C3 13.9AH C5 15.7AH C10 16.8AH C20 18.0AH |
|
Standby Use Voltage | ||
13.7 V ~ 13.9 V @ 25C | ||
Temperature Compensation: -3mV/C/Cell | ||
Cycle Use Voltage | ||
14.6 V~14.8 V @ 25C | ||
Temperature Compensation: -4mV/C/Cell | ||
Operating Temperature Range |
Discharge: -20?~60C Charge: 0C ~50C Storage: -20C~60C |
|
Normal Operating Temperature Range | 25C±5C | |
Self Discharge |
Crown Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25? and then recharging is recommended. Monthly Self-discharge ratio is less than 3% at 25?.Please charge batteries before using. |
|
Container Material | A.B.S. UL94-HB, UL94-V0 Optional. |