In compare 0 items

CMUS-9015

This UPS series is designed for places where the three-phase input and single phase output, thereby providing centralized protection for various critical equipment with capacity up to 30kVA.†UPS system with three phase input and single-phase output allows you to load more evenly industrial network, using all three phases.

Features:

  • LCD-display
  • Pure sine output
  • Case type (TOWER)
  • UPS On-line class
  • PF - 0.9
  • On Self Test
  • Cold start
  • Microprocessor control
  • Wide input voltage range
  • We solve the adaptation to the current frequency
  • Convection mode current frequencies
  • Adjustable battery charge current
  • The presence of EPO plugs for quick emergency power off
  • Availability management ports: USB, RS-232, SNMP
  • Protection against short-circuit, overload and other interference in the input power
  • Connecting additional battery cabinets
  • A parallel operation function



Where to buy Compare


Acquire

To purchase this product and delivery methods
contact your sales specialist.
Rely on professionals!


Sales department


Presentations

Check out the range of our products in the presentation section.
If you have any questions, please contact a sales specialist.

View presentation

Technology

UPS Type

On-line

Execution

Form Factor

Tower

Number of phases

Specification

3 phase input to ground and one phase output from the ground

Input parameters

Power

15.0 kW / 13.5 kW

Input voltage

380/400 V

Input voltage range

190 - 520

Current frequency

40 -70 Hz (auto-sensing)

Output parameters

Output voltage

220/230/240 V ± 1%

Form voltage

pure sine wave

Current frequency

50/60 Hz ± 0,1%

Automatic voltage regulation (AVR)

Yes

Switching time

0 ms

Power factor correction

0,9

Harmonic voltage fluctuations

<2% (linear load) and <5% (with a non-linear load)

Crest factor

3:1

Protection and UPS equipment

Surge Protection

Yes

Overload protection

Yes

UPS Login

Circuit breaker

Short circuit

Immediate load shedding or tripping of upstream circuit breaker

Protect the phone, fax, modem, LAN

No

Ports and interfaces

Dry contacts (AS-400)

Optionally

USB-port

Determination of low battery, control schedule power on / off the UPS, monitoring of input and output voltages

RS-232

Determination of low battery, control schedule power on / off the UPS, monitoring of input and output voltages

RS-485

Optionally

Port emergency shutdown EPO

Yes

SNMP

Built-in expansion slot for SNMP adapter

Connections of the generator input

Yes

Parallel UPS connection

Yes

Battery

A type

Lead-acid, sealed, maintenance-free

Voltage and battery capacity

No (only for ext. Battery cabinet)

Typical recharge time

-

Charging Current (Max)

1A -7A

Estimated battery backup time (at 50% load)

-

Estimated battery backup time (at 100% load)

-

Hot-swappable batteries

No

Connecting additional battery cabinets

Yes

Cold start

Yes

Battery protection

Automatic diagnostics, protection against overcharge and short-circuit

Physical parameters

Output connectors

-

Dimensions (W * D * B) mm

262x580x628

Weight, kg

38,5

Indication

LED and LCD-display (input / output voltage, frequency input / output voltage Operating modes: normal, bypass, battery power, battery level, load level)

Sound alarm

Beep in battery mode, when the battery is low, overload and fault charger

Case features

meterial

Metal

Protection class

IP20

Environmental Parameters

Acoustic noise

<58 dB (at 1 meter from surface)

Working conditions

Humidity 0 ~ 95% non-condensing, temperature 0 ~ 40? C

Guarantee

Standard warranty

1 year

All sections